PRODUCTS

As it surges forward, Taihua Instrument will always follow the path of enterprise development that emphasizes intelligent innovation
and continuous transcendence, promoting "Made in China" to the future and the world.

Home - Products - Product Center
Slide down

TS-SV/A series of intelligent voltage/current signal isolators

  • Type

    TS

  • Number of Input Channels

    3

  • Typical Input Signals

    AC 0-20A

  • Number of Output Channels

    2

  • Typical Output Signals

    4-20mA,0-10V

  • Power Supply

    DC24V

  • Additional Function

Contact us0557-3042599
Online message
Product details
Product details

TS-SV/A series intelligent voltage/current signal isolator, the voltage or current signal from the industrial site, through the isolated transmission output standard current/voltage signal to the control room, PLC, display instrument and DCS.

Through miniUSB interface to connect PC host computer to input signal type, range, alarm output value; Output range, type, etc. RS485 communication function (need to be customized)

The product needs independent power supply, using DIN35mm standard guide rail independent installation mode (optional bus power supply function); The input, output and power supply are isolated from each other.


14.jpg



Product parameter
Product parameter

Input end

Input signal: voltage, current, millivolt signal; Power distribution: open circuit voltage :≤26V; Voltage at 20mA :≥21V; Normal working current :≤25mA(single channel).

Input impedance :≤25Ω(current input); ≥1MQ(voltage input); ≥800KΩ(millivolt input).

Over-limit alarm: the input is lower than the lower limit of the range, and the output current is about 3.8mA(when the current is output); The input is higher than the upper limit of the range, the output current is about 20.5mA(when the current is output)

Output end

Output signal: Current signal :0-20mA; Voltage signal :0-10V(current voltage signal type and range can be set by PC)

Digital signal :RS485(optional, not included by default)

Output load resistance :RL≤400Ω(output current signal); RL≥10KΩ(output voltage signal)

Basic parameter

Number of channels: 1 in 1 out, 1 in 2 out, 2 in 2 out

Power supply :DC24V, voltage range :DC18~32V

Consumption current :≤100mA(two-in two-out,24V power supply, distribution input,20mA output)

Basic accuracy :±0.1%F.S or ±0.2%F.S(20℃) subject to physical labeling.

Temperature drift :±0.01%F.S/℃(-20℃~+55℃)

Response time :≤1S(0-90%)(TYP)

Insulation strength :1500V AC/1min(between input, output and power supply)

Insulation resistance :≥100MΩ(input, output, power supply)

Operating temperature range :-20~+55℃(no condensation, no icing)

Applicable field equipment: voltage, current, millivolt signal.

Overall dimension
Overall dimension

11.jpg



Wiring diagram
Wiring diagram

Note:

1. Bus power supply and RS485 output function are optional functions, if necessary, please specify and purchase bus power supply module when ordering.

2, TS-SV/A5XX two in two out specifications without 485 output function.



Contact us

Anhui Taihua instrument Co., LTD

Add: No.8 Building, Standardization factory, circular economy Park, Yongqiao District, Suzhou City, Anhui Province

Candy Chang

Email:taihuatrade2023@163.com

Tel: +86 19718911857

WhatsApp:+86 19718911857

Amy Lv

Email:taihua_amy@163.com

Tel: +86 18705612636

WhatsApp:+86 18705612636

Website: www.th-i.com